Bus supports 35 kW

Busbar supports of the ШО (ШОП) type for a voltage of 35 kV are intended for insulation and fastening of wires, rigid busbars and electrical devices in switchgears of power stations and alternating current substations with a frequency of 50 (60) Hz.

Busbar supports for voltage 35 kV structurally consist of 2 main elements: an insulator that performs an insulating and lightning protection function and a busbar holder installed on top of the insulator and intended for fastening flexible and rigid busbars. Also, at the customer’s request, busbar supports can be equipped with a metal support post, on which an insulator with a busbar holder is fixed.

It is possible to manufacture 35 kV busbar supports in 4 designs:

ШO-35 (II*)-1 УХЛ1: bus support for voltage 35 kV with porcelain insulator with category II* (creepage distance 105 cm), design “1” (for fastening one wire), in climatic version УХЛ1 ;

ШОП-35 (II*)-1 УХЛ1: the same as in ШO-35 (II*)-1 УХЛ1, but with a polymer insulator;

ШO-35 (II*)-2 УХЛ1: the same as in ШO-35 (II*)-1 УХЛ1, but in design “2” (for fastening two wires);

ШОП-35 (II*)-2 УХЛ1: the same as ШO-35 (II*)-2 УХЛ1, but with a polymer insulator.

In all versions, creepage distance categories and wire (pipe) diameter must be specified when ordering.

Main technical characteristics

Parameter name Meaning
1 Rated voltage, kV 35
2 Highest operating voltage, kV 40,5
3 Rated voltage frequency, Hz 50
4 Test alternating short-term voltage, kV:
— dry 95
— rain 80
5 Test voltage of full lightning impulse, kV 190
6 Power frequency test voltage under dirty and humid conditions 42
7 Mechanical bending strength, kN, not less 4
8 Wind and ice-wind loads:
— permissible wind speed without ice, m/s; 40
— permissible wind speed during icy conditions with an ice wall thickness of 20 mm, m/s 15
9 Factor of mechanical strength in relation to the load from the tension of wires, taking into account wind and ice, not less 2,5
10 Seismic resistance, points on the MSK-64 scale, not less 8
11 Radio interference level, dB, no more 54
12 Leakage distance of external insulation, cm, not less, for degree of contamination:
— I; 75
— II; 95
— II*; 105
— III; 116
— IV 140