Bus supports 220 kW

Busbar supports of the ШО (ШОП) type for a voltage of 220 kV are intended for insulation and fastening of wires, rigid busbars and devices in switchgears of power stations and substations of alternating current with a frequency of 50 (60) Hz.

Busbar supports for voltage 220 kV structurally consist of 2 main elements: an insulator column that performs an insulating and lightning protection function and a busbar holder installed on top of the insulator and intended for fastening flexible and rigid busbars. Also, at the customer’s request, busbar supports can be equipped with a frame and a metal support post (prefabricated or pipe), on which an insulator with a busbar holder is fixed.

It is possible to manufacture 220 kV bus supports in 4 main designs:

ШО-220 (II*)-1 УХЛ1: busbar support for voltage 220 kV with a porcelain insulator with category II* (creepage distance 105 cm), design “1” (for fastening one wire), in climatic version УХЛ1;

ШОП-220 (II*)-1 УХЛ1: the same as in ШO-220 (II*)-1 УХЛ1, but with a polymer insulator;

ШО-220 (II*)-2 УХЛ1: the same as in ШО-220 (II*)-1 УХЛ1, but in design “2” (for fastening two wires);

ШОП-220 (II*)-2 УХЛ1: the same as ШО-220 (II*)-2 УХЛ1, but with a polymer insulator.

In all versions, creepage distance categories and wire (pipe) diameter must be specified when ordering.

Main technical characteristics

Parameter name Meaning
1 Rated voltage, kV 220
2 Highest operating voltage, kV 252
3 Rated voltage frequency, Hz 50 (60)
4 Test alternating short-term voltage, kV:
— dry 395
— rain 395
5 Test voltage of full lightning impulse, kV 950
6 Power frequency test voltage under dirty and humid conditions 220
7 Mechanical bending strength, kN, not less 4
8 Wind and ice-wind loads:
— permissible wind speed without ice, m/s; 40
— permissible wind speed during icy conditions with an ice wall thickness of 20 mm, m/s 15
9 Factor of mechanical strength in relation to the load from the tension of wires, taking into account wind and ice, not less 2,5
10 Seismic resistance, points on the MSK-64 scale, not less 8
11 Radio interference level, dB, no more 54
12 Leakage distance of external insulation, cm, not less, for degree of contamination:
— I; 405
— II; 505
— II*; 570
— III; 630
— IV 790