Bus supports 150 kW
Bus supports of the ШО (ШОП) type for a voltage of 150 kV are intended for insulation and fastening of wires, rigid busbars and devices in switchgears of power stations and substations of alternating current with a frequency of 50 (60) Hz.
Busbar supports for a voltage of 150 kV are structurally composed of 2 main elements: a column of insulators (or one insulator), which performs an insulating and lightning protection function, and a busbar holder installed on top of the insulator and intended for fastening flexible and rigid busbars. Also, at the customer’s request, busbar supports can be equipped with a frame and a metal support post, on which an insulator with a busbar holder is fixed.
It is possible to manufacture 150 kV busbar supports in 4 main designs:
ШО-150 (II*)-1 УХЛ1: busbar support for voltage 150 kV with a porcelain insulator with category II* (creepage distance 105 cm), design “1” (for fastening one wire), in climatic version УХЛ1;
ШОП-150 (II*)-1 УХЛ1: the same as in ШО-150 (II*)-1 УХЛ1, but with a polymer insulator;
ШO-150 (II*)-2 УХЛ1: the same as in ШО-150 (II*)-1 УХЛ1, but in design “2” (for fastening two wires);
ШОП-150 (II*)-2 УХЛ1: the same as ШO-150 (II*)-2 УХЛ1, but with a polymer insulator.
In all versions, creepage distance categories and wire (pipe) diameter must be specified when ordering.
Main technical characteristics
| № | Parameter name | Meaning |
| 1 | Rated voltage, kV | 150 |
| 2 | Highest operating voltage, kV | 172 |
| 3 | Rated voltage frequency, Hz | 50 (60) |
| 4 | Test alternating short-term voltage, kV: | |
| — dry | 275 | |
| — rain | 275 | |
| 5 | Test voltage of full lightning impulse, kV | 650 |
| 6 | Power frequency test voltage under dirty and humid conditions | 150 |
| 7 | Mechanical bending strength, kN, not less | 4 |
| 8 | Wind and ice-wind loads: | |
| — permissible wind speed without ice, m/s; | 40 | |
| — permissible wind speed during icy conditions with an ice wall thickness of 20 mm, m/s | 15 | |
| 9 | Factor of mechanical strength in relation to the load from the tension of wires, taking into account wind and ice, not less | 2,5 |
| 10 | Seismic resistance, points on the MSK-64 scale, not less | 8 |
| 11 | Radio interference level, dB, no more | 54 |
| 12 | Leakage distance of external insulation, cm, not less, for degree of contamination: | |
| — I; | 270 | |
| — II; | 340 | |
| — II*; | 390 | |
| — III; | 425 | |
| — IV | 535 |