Unified vibration dampers of the HLG type are designed to protect against vibration of uninsulated wires and lightning protection cables of overhead power lines, as well as self-supporting fiber-optic communication cables.
![]() |
![]() |
G – extinguisher;
B – vibrations;
Y – unified;
P1 - the presence of a protector;
m1 and m2 – cargo weight, m1 ≠ m2, kg;
d – diameter of the damper cable, mm;
L – length of the damper, mm;
M1 - modification of the die of the extinguisher:
1 – interval of diameters of wires (cables) from 9 to 18 mm;
2 – interval of diameters of wires (cables) from 18 to 29 mm;
3 – the interval of diameters of wires (cables) from 28 to 38 mm.
The standard supply of a vibration damper of the GVU type protector is not included and is ordered separately.Damper brand Vibration | Cargo weight, kg | Damper length L, mm | L1, mm | L2, mm | Dia-meter of cable d, mm | Diameter of wire (cable), mm | Н, mm | Range frequencies, Hz | |
m1 | m2 | ||||||||
HLG-0,6-0,8-9,1-400/1 | 0,6 | 0,8 | 400 | 180 | 220 | 9,1 | 9,0-18,0 | 69 | 12-70 |
HLG-0,6-0,8-9,1-400/2 | 0,6 | 0,8 | 400 | 180 | 220 | 9,1 | 18,1-29,0 | 84 | 12-70 |
GVU-1,2-1,6-11-450/1 | 1,2 | 1,6 | 450 | 200 | 250 | 11 | 9,0-18,0 | 69 | 10-55 |
HLG-1,2-1,6-11-450/2 | 1,2 | 1,6 | 450 | 200 | 250 | 11 | 18,1-29,0 | 84 | 10-55 |
HLG-1,6-2,4-11-500/1 | 1,6 | 2,4 | 500 | 220 | 280 | 11 | 9,0-18,0 | 69 | 8-50 |
HLG-1,6-2,4-11-500/2 | 1,6 | 2,4 | 500 | 220 | 280 | 11 | 18,1-29,0 | 84 | 8-50 |
HLG-2,4-3,2-13-550/2 | 2,4 | 3,2 | 550 | 250 | 300 | 13 | 18,1-29,0 | 84 | 5-35 |
GVU-2,4-3,2-13-550/3 | 2,4 | 3,2 | 550 | 250 | 300 | 13 | 28,0-38,0 | 97 | 5-35 |
HLG-3,2-4,0-13-550/3 | 3,2 | 4,0 | 550 | 250 | 300 | 13 | 28,0-38,0 | 97 | 4-30 |